40-7705I-UM Page 72 Rev 4 March 16, 2007
Explanation of the Control Group Functions:
Function Explanation
TURN ON TX
• Press <ALT> + <C>
• Press <1>
• Select Target Unit
• Select Route
• Re-enables transmitting on a remote subscriber unit that
has been turned off (see Turn Off TX, next).
TURN OFF TX
• Press <ALT> + <C>
• Press <2>
• Select Target Unit
• Select Route
• Disables a remote subscriber unit should the need arise,
such as when an alarm system fails and causes the
transmitter to activate repeatedly. NOTE: The unit is not
literally turned off, but is prevented from transmitting until
it receives the "Turn On" signal (above). Also Note that a
transceiver in the Off Mode will create route failed
message when including in an outbound route.
• A reset will clear this mode and return to TX ON.
WARNING: This function disables the subscriber - use it
only when absolutely necessary.
• This function may be used on UL Burglar Alarm and Fire
Alarm systems only with strict adherence to the
requirements of UL Standard 611, Central Station Burglar
Alarm Units and the National Fire Alarm Code, NFPA 72.
REMOTE RESET
• Press <ALT> + <C>
• Press <3>
• Select Target Unit
• Select Route
• Resets the remote subscriber unit - the same as physically
pushing the reset button on the unit itself. This causes the
subscriber unit to re-enroll on the network and build a new
routing table. A reset may be used to restart the check-in
interval timer. The new interval will commence at the time
of reset (see also: subscriber unit manuals).
INTELLITAP
MESSAGES
• Press <ALT> + <C>
• Press <4>
• Select Target Unit
• Select Route
• Enter D to Disable, E to Enable Tap
Messages
• Enables / Disables the subscriber unit's ability to send
IntelliTap Messages. CAUTION: Once disabled, the
subscriber will ignore IntelliTap or FDX data presented to
its port.
• This function works with 7750-F, 7050-E (Ver 2+), 7450
and 7440 models.
• To confirm the function, perform a "Get Subscriber Mode
Data" to retrieve the current status of this mode (Message
group, # 9) and to update the database.
• Refer to subscriber unit and IntelliTap manuals for more
information.