40-7705I-UM Page 2 Rev 4 March 16, 2007
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING
JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to
comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, certain programming features or options must be limited
to specific values or not used at all as indicated below.
Program Permitted in Possible
Feature or Option UL 864 (Y/N) settings Settings permitted in UL 864
Alarm Automation Y 0-90 As configured by UL 1981
Heartbeat Signal Central-Station Automation
Frequency: Systems Requirements
Serial or IP
Data Type: Y Security, GPS, USDI, Security
Others in pull down menu
Old Alarm Delivery Y All, Subscriber controlled
Options Never All
Radio Packet Life Y 0-99 0 – No Time Out for Alarm, Trouble
or Restoral
Notes:
For Alarm Automation references throughout this manual,
Alarm Automation output must be connected to a
UL 1981 Listed Alarm Automation System
For UL Central Station Burglar Alarm applications,
Opening/Closing Signals shall be sent using an alternate communication
means that provides for premises acknowledgement (ring back)
This product shall be installed in accordance with NFPA 72,
NEC, UL 827 and all applicable local codes
For compliance with UL Central Station Burglar Alarm applications,
a workstation is required to be able to determine subscriber status.
The workstation shall be UL Listed ITE equipment.